قائمة المنتجات
Stainless steel sterilization boxes
Content:
Stainless steel sterilization boxes are used as an aid to clean the room. It is used to pass small parts
Of clean places, between clean and non-clean areas. In this way, the number of times the door is opened is reduced, and the percentage of pollution in the room decreases.
The box is made of stainless steel and has UV lamp and inner lock
electronic.
Performance requirements:
1. The level of internal cleanliness is "B".
2. Internal layers, internal arc processes.
3. Stainless steel sterilization boxes are designed by negative pressure method. The air is sent up and the air is down. While the side air contains the design of the hole of stainless steel "SUS304".
4. Filter: The primary filter consists of G4, HEPA contains H14, and has a productivity up to 99.99%.
5. Air speed: The air speed is controlled between 0.3-0.4m / s (using the air-flow control orifice plate, 150 mm).
6. Ability to distinguish pressure. The ability to display the pressure filter (range from 0-500Pa), accurately ± 5Pa.
7. Control function: control buttons, electronic lock, UV lamp.
8. The possibility of installing and removing "HEPA" on its own.
9. There is a fan slot above the box, to facilitate the replacement process.
10. Noise level: The sound level of the box is <65db.
11. The air flow control system - orifice plate - is made of SUS304 stainless steel material.